The Real Estate License Act
§535.227. Standards of
Practice:
(a) Definition of
terms. The following words have the following meanings, unless the context
clearly indicates otherwise.
(1) Act - The Real
Estate License Act, Article 6573a, Texas Civil Statutes.
(2) Functioning -
Performing in an expected or required manner; carrying out the design
purpose or intended operation of a part, system, component, member.
(3) Inaccessible - Not
having access without the use of special tools, equipment, or instruments,
or removing doors, walls, stored items or similar obstructions, or by
causing damage to a structure, finish or component, equipment or system,
or by virtue of inadequate clearance, walkways, passageways, or hazardous
condition.
(4) In Need of Repair
- Does not adequately function or perform.
(5) Inspect - To look
at and examine accessible items, parts, systems or components without,
except as required by the rules of the Texas Real Estate Commission,
laboratory, scientific or engineering evaluation or testing, destructive
tests or the dismantling or removal of parts, members or components.
(6) Inspector - A
person licensed as a professional inspector, a person licensed as an
apprentice inspector or a person licensed as a real estate inspector.
(7) Performance - The
act of carrying out, completing, executing or achievement of an operation,
design or function in a manner consistent with the intent of the
manufacturer, designer or accepted industry practice.
(8) Report - A written
or oral communication of the inspector’s opinions, observations,
determinations, and findings in an inspection.
(9) Standards of
Practice - §535.227 of this title (relating to Standards of Practice:
General Provisions), §535.228 of this title (relating to Standards of
Practice: Inspection Guidelines for Structural Systems, §535.229 of this
title (relating to Standards of Practice: Inspection Guidelines for
Mechanical Systems: Appliances, Cooling Systems, Heating Systems, Ducts,
Vents and Flues, and Plumbing Systems), §535.230 of this title (relating
to Standards of Practice: Inspection Guidelines for Electrical Systems)
and §535.231 of this title (relating to Standards of Practice: Optional
Systems).
(b) Scope.
(1) The standards of
practice are the minimum levels of inspection practice required of
inspectors for the accessible parts, components, and systems typically
found in improvements to real property, excluding detached structures,
decks, docks and fences. The inspector may provide a higher level of
inspection performance than required by the standards of practice and may
inspect parts, components, and systems in addition to those described by
the standards of practice.
(2) The inspector
shall:
(A) inspect items,
parts, systems, components and conditions which are present and visible at
the time of the inspection, but the inspector is not required to determine
or estimate the remaining life expectancy or future performance of any
inspected item, part, system or component;
(B) operate mechanical
and electrical equipment, systems, and appliances during an inspection in
normal modes and operating range at the time of the inspection;
(C) report which of
the parts, components, and systems present in the property have or have
not been inspected;
(D) report as in need
of repair inspected parts, components or systems that are not functioning
or that the standards of practice require the inspector to report as in
need of repair;
(E) address all of the
parts, components, and systems contained in the standards of practice in
the property being inspected.
(F) complete the
standard inspection report form under §535.223 of this title (relating to
Standard Inspection Reports) if that section applies;
(G) identify in any
written report the inspector who performed the inspection by name and
license number;
(H) comply with any
other law or license requirement necessary to perform inspections or
services other than what is required by the standards of practice, such as
an air-conditioning and refrigeration contractor license which may be
required for the inspector to make a direct in-line connection to a
refrigerant system, or a structural pest control license which may be
required to perform a wood-destroying-insect inspection;
(3) In the event of a
conflict between a specific provision and a general provision in the
standards of practice, the specific provision controls. The standards of
practice do not apply to the following:
(A) parts, components
or systems other than those specifically described;
(B) conditions other
than those specifically described, such as environmental conditions,
presence of toxic or hazardous wastes or substances, presence of termites
or other wood-destroying insects or organisms, compliance with codes,
ordinances, statutes or restrictions or the efficiency, quality,
durability of any item inspected;
(C) any part,
component or system the inspector excludes under the departure provision
in this section; and
(D) any determination
of insurability or warrantability of any part, component or system.
(c) Departure
Provision.
(1) An inspector shall
exclude from the inspection any part, component or system which the
inspector is not competent or qualified to inspect.
(2) An inspector may
exclude any part, component or system required for inspection by the
standards of practice which is inaccessible, cannot be inspected due to
circumstances beyond the control of the inspector, or the inspector’s
client has agreed is not to be inspected.
(3) This departure
provision does not prohibit an inspector from specializing nor require the
inspector to specifically exclude other parts, components or systems not
ordinarily considered a part of the inspector’s specialty. However, the
inspector shall comply with the standards of practice for the items being
inspected.
(4) If an inspector
excludes any part, component or system listed in the standards of
practice, other than one which the client has agreed is not to be
inspected, the inspector shall:
(A) advise the client
at the earliest practicable time that the specific part, component or
system will not be included in the inspection; and
(B) state in any
written inspection report that the excluded part, component or system was
not inspected.
(d) Enforcement.
Failure to comply with §535.227 of this title (relating to Standards of
Practice: General Provisions), §535.228 of this title (relating to
Standards of Practice: Inspection Guidelines for Structural Systems,
§535.229 of this title (relating to Standards of Practice: Inspection
Guidelines for Mechanical Systems: Appliances, Cooling Systems, Heating
Systems, Ducts, Vents and Flues, and Plumbing Systems), §535.230 of this
title (relating to Standards of Practice: Inspection Guidelines for
Electrical Systems) and §535.231 of this title (relating to Standards of
Practice: Optional Systems) is a ground for disciplinary action as
prescribed by the Act, §23 (1)(7) and §535.224 of this title (relating to
Proceedings before the Committee).
§535.228. Standards of
Practice: Inspection Guidelines for Structural Systems.
(a) Foundations. The
inspector shall:
(1) report the type of
foundation (for example, slab-on-grade or pier and beam);
(2) inspect the
foundation, related structural components and/or slab surfaces;
(3) inspect the crawl
space area to determine the general condition of foundation components and
report the method used to observe the crawl space if the inspector did not
enter the crawl space because the space was inaccessible, hazardous
conditions were present, or access or visibility was limited;
(4) render a written
opinion as to the performance of the foundation;
(5) report general
indications of foundation movement that are present and visible, such as
sheetrock cracks, brick cracks, out-of-square door frames or floor slopes;
(6) report as in need
of repair any post tensioned cable ends that are not protected;
(7) report as in need
of repair a crawl space that does not appear to be adequately ventilated;
(8) report as in need
of repair conditions or symptoms that may indicate the possibility of
water penetration that are present and visible, such as improper grading
around foundation walls or plumbing leaks; and
(9) report as in need
of repair conditions that are present and visible and may be adversely
affecting foundation performance, such as erosion or water ponding.
(b) Specific limitations for
foundations. The inspector is not
required to enter a crawl space or any areas where headroom is less than
18 inches and the width of the access opening is less than two feet, or
where the inspector reasonably determines conditions or materials are
hazardous to health or safety of the inspector.
(c) Interior walls,
doors, ceilings and floors. The inspector shall:
(1) report as in need
of repair deficiencies of the surfaces of walls, ceilings and floors as
related to structural performance or water penetration that are present
and visible;
(2) report as in need
of repair accessible doors that do not operate properly, excluding locks
and latches;
(3) report as in need
of repair deficiencies in steps, stairways, balconies and railings,
(4) report as in need
of repair spacings between intermediate balusters, spindles, or rails for
steps, stairways, balconies, and railings that permit passage of an object
greater than four inches in diameter; and
(5) report as in need
of repair the absence of safety glass in hazardous locations.
(d) Specific limitations for
Interior walls, doors, ceilings and floors.
The inspector is not required to do the following:
(1) determine the condition of
floor, wall or ceiling coverings unless such conditions affect structural
performance or indicate water penetration;
(2) report obvious damage to
floor, wall or ceiling coverings;
(3) determine the condition of
paints, stains and other surface coatings; or
(4) determine condition of
cabinets.
(e) Exterior walls and
doors, windows and door glazing. The inspector shall:
(1) report as in need
of repair present and visible deficiencies of exterior walls that are
related to structural performance and water penetration;
(2) report as in need
of repair deficiencies in the condition and operation of exterior doors
and garage doors, including door locks and latches when present.
(3) report as in need
of repair damaged glazing in windows and exterior doors;
(4) report as in need
of repair any insulated windows that are obviously fogged or display other
evidence of broken seals;
(5) report as in need
of repair the absence of safety glass in hazardous locations;
(6) report as in need
of repair missing or damaged window and door screens;
(7) report as in need
of repair in homes having burglar bars the absence of functional keyless
burglar bars in appropriate locations;
(8) report as in need
of repair inoperable windows at burglar bar locations of sleeping rooms or
egress areas and any inoperable windows at other randomly sampled
accessible burglar bar locations; and
(9) report as in need
of repair spacings between intermediate balusters, spindles and rails that
permit passage of an object greater than four inches in diameter.
(f) Specific limitations for
exterior walls and doors, windows and door glazing.
The inspector is not required to do the following:
(1) report the condition or
presence of storm windows or doors, awnings, shutters or security devices
or systems;
(2) determine the condition of
paints stains or other surface coatings; or
(3) determine the presence of, or
extent or type of, insulation or vapor barriers in exterior walls.
(g) Fireplace and
chimney. The inspector shall:
(1) report as in need
of repair deficiencies in the visible components and structure of the
chimney and fireplace;
(2) inspect the
interior of the firebox and the visible flue area, and report as in need
of repair built up creosote in visible areas of the firebox and flue (the
inspector is not required to determine the adequacy of the draft or
perform a chimney smoke test);
(3) report as in need
of repair a damper that does not operate;
(4) report as in need
of repair the presence of non-combustible hearth extension;
(5) report as in need
of repair deficiencies in the lintel, hearth and material surrounding the
fireplace, including clearances from combustible materials;
(6) report as in need
of repair the absence of fire-stopping at the attic penetration of the
chimney flue, where accessible;
(7) report as in need
of repair any gas log lighter valves that do not function or leak gas;
(8) report as in need
of repair any circulating fan that does not operate, if present;
(9) report as in need
of repair deficiencies in combustion air vent, if present; and
(10) report as in need
of repair deficiencies in chimney coping or crown, caps or spark arrestor
(inspected from ground level at a minimum).
(h) Roof, roof
structure and attic. The inspector shall:
(1) report the type of
roof covering and report as in need of repair:
(A) a roof covering
that is not appropriate for the slope of the roof;
(B) fasteners that are
not present or that are not appropriate, (where it can be reasonably
determined); and
(C) roof jacks,
flashing and counter flashing that are not present or not properly
installed.
(2) inspect the
general condition of, and report evidence of previous repairs to,
flashing, skylights and other roof penetrations;
(3) report as in need
of repair inadequate attic space ventilation;
(4) report as in need
of repair deficiencies in the roof covering, structure and sheathing;
(5) report any visible
evidence of moisture penetration;
(6) report as in need
of repair the lack of or inappropriate installation of components such as
purlins, struts, collar ties or rafter ties, where necessary;
(7) report as in need
of repair excessive deflections or depressions in the roof’s surface
relating to the performance of the framing and the roof deck;
(8) enter and inspect
attic space(s) except when inadequate access or hazardous conditions exist
as reasonably determined by the inspector and report the method used to
inspect the attic if the inspector did not enter the attic;
(9) report the method
used to inspect the roof if the inspection is performed from other than
roof level;
(10) inspect for the
presence, and report the approximate depth of, insulation where visible;
and
(11) report as in need
of repair deficiencies in visible installed gutter and downspout systems.
(i) Specific limitations for
roof, roof structure and attic.
The inspector is not required to do the following:
(1) determine the remaining life
expectancy of the roof covering; or
(2) inspect the roof from the
roof level if the inspector reasonably determines that the inspector
cannot safely reach or stay on the roof, or that damage to the roof or
roof covering may result from walking on the roof.
(j) Porches and decks.
The inspector shall:
(1) report as in need
of repair structural deficiencies in porches, decks, steps, balconies and
carports as to visible footings, joists, deckings, railings and attachment
points, where applicable; and
(2) report as in need
of repair (except for decks which are not higher than 30 inches as
measured from the adjacent grade) spacings between intermediate balusters,
spindles or rails that permit passage of an object greater than four
inches in diameter.
(k) Specific limitations for
porches and decks. The inspector
is not required to inspect detached structures or waterfront structures
and equipment, such as docks or piers.
§535.229. Standards of
Practice: Inspection Guidelines for Mechanical Systems: Appliances,
Cooling Systems, Heating Systems, Ducts, Vents and Flues, and Plumbing
Systems.
(a) Dishwasher. The
inspector shall:
(1) report as in need
of repair any deficiencies in the door gasket, control knobs and
interior parts, including the dish tray, rollers, spray arms and the soap
dispenser;
(2) report as in need
of repair any interior signs of rust;
(3) report as in need
of repair a door spring that does not operate properly;
(4) report as in need
of repair deficiencies in the discharge hose or piping or the lack of back
flow prevention;
(5) report as in need
of repair units that are not securely mounted;
(6) report as in need
of repair any water leaks;
(7) inspect the unit’s
operation in normal mode with the soap dispenser closed; and
(8) report as in need
of repair spray arms that do not turn, soap dispensers that do not open or
drying elements that do not operate.
(b) Food waste
disposer. The inspector shall:
(1) report as in need
of repair any deficiencies in the splash guard, grinding components,
wiring and exterior;
(2) report as in need
of repair a unit that is not securely mounted; and
(3) inspect the
operation of the unit and report as in need of repair any unusual noise or
vibration level and any signs of water leaks.
(c) Range exhaust
vent. The inspector shall:
(1) report as in need
of repair any deficiencies in the filter, vent pipe, light and switches;
(2) inspect the
operation of the blower and report as in need of repair any unusual sounds
or vibration levels, or if the blower does not operate at all speeds;
(3) report as in need
of repair a vent pipe that does not terminate outside the structure when
the unit is not of recirculating type or configuration.
(4) report as in need
of repair a vent pipe that is of inadequate material; and
(5) report as in need
of repair the absence of a range exhaust vent.
(d) Electric or gas
ranges. The inspector shall:
(1) report as in need
of repair broken or missing knobs, elements, drip pans or other parts,
inadequate clearance from combustible material, or the absence of an
anti-tip device;
(2) report as in need
of repair signal lights and elements or burners that do not operate at low
and high settings;
(3) report as in need
of repair improper materials that are used for the gas branch line and the
connection to the appliance; and
(4) report as in need
of repair the absence of a gas shut-off valve, or valve that is not
properly located, is inaccessible, or leaks.
(e) Electric or gas
ovens. The inspector shall:
(1) report as in need
of repair any broken or missing knobs, handles, glass panels, door hinges,
lights or light covers or other parts, or inadequate clearance from
combustible material;
(2) report as in need
of repair deficiencies in the door gasket, tightness of closure and
operation of the latch;
(3) report as in need
of repair an oven that is not securely mounted;
(4) report as in need
of repair heating elements and thermostat sensing elements that are not
properly supported;
(5) report as in need
of repair deficiencies in the operation of the heating elements or the
lighting, operation and condition of the flame;
(6) report as in need
of repair deficiencies in the operation of the clock and timer, thermostat
and door springs; and
(7) report as in need
of repair any inaccuracy of the thermostat more than a 25 degree range
plus or minus of a 350 degree setting, as measured by a thermometer.
(f) Microwave oven.
The inspector shall:
(1) report as in need
of repair any broken or missing knobs, handles, glass panels, or other
parts, or a unit that is not securely mounted;
(2) report as in need
of repair any deficiencies in the door and seal (the inspector is not
required to test for radiation);
(3) report as in need
of repair an oven that does not operate by heating a container of water or
with other test equipment, as reasonably determined by the inspector; and
(4) report as in need
of repair a light that does not operate.
(g) Trash compactor.
The inspector shall:
(1) inspect the
overall condition of the unit;
(2) report as in need
of repair a unit that does not operate or operates with unusual noise or
vibration levels; and
(3) report as in need
of repair a unit that is not securely mounted in place.
(h) Other built-in
appliances. The inspector shall report as in need of repair any
deficiencies in condition or operation of other built-in appliances not
listed in this section.
(i) Bathroom exhaust
vents and electric heaters. The inspector shall operate the unit, and
report as in need of repair unusual sounds, speed and vibration levels or,
when possible, vent pipes that do not terminate outside the structure.
(j) Whole house vacuum
system. The inspector shall:
(1) inspect the
condition of the main unit;
(2) report as in need
of repair a unit that does not operate; and
(3) inspect the system
from all accessible outlets throughout the house.
(k) Water heaters. The
inspector shall:
(1) report the energy
source;
(2) inspect the unit
and report as in need of repair fittings that leak or are corroded;
(3) report as in need
of repair temperature and pressure relief valve piping that lacks gravity
drainage, is improperly sized (no smaller than the outlet fittings), has
deficiencies in material, or lacks a correct termination;
(4) report as in need
of repair a temperature and pressure relief valve that does not operate
when the valve is of an operable type and operation will not cause damage
to persons or property as reasonably determined by the inspector (for
example, it would be reasonable not to operate the valve if there is
improper or undetermined termination of the drain pipe, a corroded or
damaged valve, improper installation of valve or drain pipe, the drain
pipe is of inappropriate material or there is no water supply cut-off
valve at the unit);
(5) report as in need
of repair any broken or missing parts, covers or controls;
(6) report as in need
of repair deficiencies in the burner, flame and burner compartment, the
operation of heating elements and the condition of wiring;
(7) report as in need
of repair deficiencies in materials used for the gas branch line and the
connection to the appliance, the absence of a gas shut-off valve, or a
valve that is not properly located, is inaccessible, or leaks;
(8) if applicable,
report as in need of repair deficiencies in the vent pipe, draft diverter,
draft hood and their condition, draft, proximity to combustibles and vent
termination point, observing for adequate combustion and draft air;
(9) report as in need
of repair the lack of a safety pan and drain (including the termination of
the drain line) when applicable;
(10) report as in need
of repair an unsafe location or installation; and
(11) inspect garage
units or units which are located in rooms or enclosures opening into a
garage and report as in need of repair the following:
(A) a lack of
protection for physical damage to the unit; and
(B) burners, burner
ignition devices or heating elements, switches or thermostats that are not
a minimum of 18 inches above the lowest garage floor elevation.
(l) Doorbell and
chimes. The inspector shall:
(1) inspect the
condition of the unit and report as in need of repair a unit that does not
operate; and
(2) report as in need
of repair any deficiencies in visible and accessible parts.
(m) Attic power vents.
The inspector shall:
(1) report as in need
of repair deficiencies in the operation and installation of the unit,
including the wiring and mounting of the thermostat control, if so
equipped and accessible; and
(2) report as in need
of repair unusual sounds or speed and vibration levels.
(n) Garage door
operator. The inspector shall:
(1) report as in need
of repair deficiencies in the installation, condition and operation of the
garage door operator;
(2) operate the door
both manually and by an installed automatic door control;
(3) report as in need
of repair a door that does not automatically reverse during closing cycle,
any installed electronic sensors that are not operable or not installed at
the proper heights above the garage floor ; and
(4) report as in need
of repair door locks or side ropes that have not been removed or
disabled.
(o) Hydrotherapy or
whirlpool equipment. The inspector shall:
(1) report as in need
of repair a unit that does not operate, leaks, or is inaccessible;
(2) report as in need
of repair a unit that lacks a ground fault circuit interrupter or has an
interrupter that does not operate;
(3) report as in need
of repair switches that are not in a safe location or do not operate;
(4) report evidence of
leaks under the tub if the access cover is available and accessible,
reporting when the cover is absent or inaccessible (the inspector is not
required to determine the adequacy of self-draining features of the
circulation system); and
(5) report as in need
of repair deficiencies in the ports, valves, grates and covers.
(p) Specific limitations for
appliances. The inspector is not
required to do the following:
(1) operate or determine the
condition of other auxiliary components of inspected items; or
(2) inspect self-cleaning
functions.
(q) Cooling systems
other than evaporative coolers. The inspector shall:
(1) report the type of
system and energy sources;
(2) operate the system
using normal control devices except when the outdoor temperature is less
than 60 degrees Fahrenheit;
(3) inspect for proper
performance; such as by observing the temperature difference between the
supply air and the return air or noticeable vibration of the blower fan
and report as in need of repair any deficiencies;
(4) report as in need
of repair the lack of, or deficiencies in drainage of, condensate drain
line and secondary drain line when applicable, including pipes made of
inadequate material;
(5) report as in need
of repair a primary drain pipe that terminates in a sewer vent, if the
termination is visible;
(6) report as in need
of repair a safety pan that is not appropriately sized for the evaporator
coil or free of water or debris;
(7) report as in need
of repair a return chase and plenum that are not free of improper and
hazardous conditions, such as gas pipes, sewer vents, refrigerant piping
or electrical wiring.
(8) report as in need
of repair the lack of insulation on refrigerant pipes and the primary
condensate drain pipe;
(9) report as in need
of repair a condensing unit that does not have adequate clearances, or air
circulation, or that has deficiencies in the condition of fins, location,
levelness and elevation above ground surfaces; and
(10) report as in need
of repair conductor sizing and over-current protective devices that are
not appropriately sized for the unit.
(r) Evaporative
coolers. The inspector shall:
(1) operate the motor
and report as one or two speed;
(2) observe the
electrical pigtail connection at the motor
(3) inspect the power
source in the unit;
(4) report as in need
of repair a pump that does not function or deficiencies in the spider
tubes, tube clips and bleeder system;
(5) report as in need
of repair deficiencies in the water supply line and float bracket;
(6) report as in need
of repair the absence of a minimum one-inch air gap between water
discharge at float and water level;
(7) report as in need
of repair deficiencies in the fan (blower) and squirrel cage or rust
build-up, deterioration or corrosion;
(8) report as in need
of repair deficiencies in the fan belt and pulleys;
(9) report as in need
of repair deficiencies in the housing side panels, the water trays, the
exterior housing and the roof frame;
(10) report as in need
of repair deficiencies in the roof jack or other mounting point and the
location of the seasonal damper at the unit; and
(11) report as in need
of repair deficiencies in the interior registers and the supply duct.
(s) Specific limitations for
cooling systems. The inspector is
not required to do the following:
(1) inspect for the pressure of
the system coolant or determine the presence of leaks;
(2) program digital-type
thermostats or controls; or
(3) operate setback features on
thermostats or controls.
(t) Heating systems.
The inspector shall:
(1) report the type of
heating system and its energy sources;
(2) report as in need
of repair a system that does not operate properly using normal control
devices;
(3) report as in need
of repair deficiencies in the controls and accessible operating components
of the system;
(4) in gas units,
inspect the burner, and report as in need of repair deficiencies in the
burner compartment, type, condition, draft and termination of the vent
pipe, or proximity to combustibles; the lack of combustion and draft air
or inappropriate location, or the lack of forced air in the burner
compartment (full evaluation of the integrity of a heat exchanger requires
dismantling of the furnace and is beyond the scope of a visual
inspection);
(5) report as in need
of repair gas units that display flame impingement, uplifting flame,
improper flame color or excessive scale buildup;
(6) report as in need
of repair gas units that use improper materials for the gas branch line
and the connection to the appliance;
(7) report as in need
of repair in gas units deficiencies in materials used for the gas branch
line and the connection to the appliance, the absence of a gas shut-off
valve, or a valve that is not properly located, is inaccessible, or leaks;
and
(8) report as in need
of repair elements in electric furnaces that do not operate;
(9) report as in need
of repair a return chase or plenum that are not free of improper and
hazardous conditions, such as gas pipes, sewer vents, refrigerant piping
or electrical wiring; and
(10) report if the
inspector deemed the furnace to be inaccessible.
(u) Specific limitations for
heating systems. The inspector is
not required to do the following:
(1) inspect accessories such as
humidifiers, air purifiers, motorized dampers, heat reclaimers, electronic
air filters or wood-burning stoves;
(2) determine the efficiency or
adequacy of a system;
(3) program digital-type
thermostats or controls; or
(4) operate radiant heaters,
steam heat systems or unvented gas-fired heating appliances.
(v) Ducts, vents
(including dryer vents) and flues. The inspector shall:
(1) report as in need
of repair deficiencies such as damaged ducting or insulation, improper
material or improper routing of ducts where visible and accessible;
(2) report as in need
of repair the absence of air flow at all accessible supply registers in
the habitable areas of the structure;
(3) report as in need
of repair deficiencies in accessible duct fans and filters;
(4) report as in need
of repair deficiencies in installation, such as gas piping, sewer vents,
electrical wiring or junction boxes in the plenum, returns or chases or
improper sealing, where visible;
(5) report as in need
of repair deficiencies in the flue system components;
(6) report as in need
of repair a flue or vent pipe that does not properly terminate; and
(7) report as in need
of repair deficiencies in materials used for the venting systems.
(w) Specific limitations for
ducts and vents. The inspector is
not required to do the following:
(1) determine the efficiency,
adequacy or capacity of the systems;
(2) determine the uniformity of
the supply of conditioned air to the various parts of the structure;
(3) determine the types of
materials contained in insulation, wrapping of pipes, ducts, jackets,
boilers and wiring;
(4) operate venting systems
unless ambient temperatures or other circumstances, in the reasonable
opinion of the inspector, are conducive to safe operation without damage
to the equipment; or
(5) operate a unit outside its
normal operating range as reasonably determined by the inspector.
(x) Plumbing systems.
The inspector shall:
(1) inspect and report
as in need of repair deficiencies in the type and condition of all
accessible and visible water supply and waste-water and vent pipes;
(2) inspect and report
as in need of repair deficiencies in the operation of all fixtures and
faucets where the flow end of the faucet is not connected to an appliance;
(3) report as in need
of repair the lack of back-flow devices, anti-siphon devices or systems or
air gaps when applicable;
(4) report as in need
of repair incompatible materials in connecting devices between differing
metals in the supply system, where visible;
(5) report as in need
of repair deficiencies in water supply by viewing functional flow in two
fixtures operated simultaneously;
(6) report as in need
of repair deficiencies in functional drainage at accessible plumbing
fixtures;
(7) report as in need
of repair deficiencies in installation and identification of hot and cold
faucets;
(8) report as in need
of repair mechanical drain stops that are missing or do not operate if
installed on sinks, lavatories and tubs;
(9) report as in need
of repair commodes that have cracks in the ceramic material, are
improperly mounted on the floor, leak or have tank components which do not
operate;
(10) report as in need
of repair accessible supply and drain pipes that leak;
(11) report as in need
of repair the lack of a visible vent pipe system to the exterior of the
structure or improper routing or termination of the vent system;
(12) report as in need
of repair a shower enclosure that leaks; and
(13) report as in need
of repair any exterior faucet attached or immediately adjacent to the
structure that does not operate properly.
(y) Specific limitations for
plumbing systems. The inspector
is not required to do the following:
(1) operate any main, branch or
shut-off valves;
(2) inspect any system that has
been shut down or otherwise secured;
(3) inspect any components that
are not visible or accessible;
(4) inspect any exterior plumbing
components such as water mains, private sewer systems, water wells,
sprinkler systems or swimming pools;
(5) inspect fire sprinkler
systems;
(6) inspect or operate drain
pumps or waste ejector pumps;
(7) inspect the quality or the
volume of well water;
(8) determine the potability of
any water supply;
(9) inspect water-conditioning
equipment, such as softeners or filter systems;
(10) inspect solar water heating
systems;
(11) determine the effectiveness
of anti-siphon devices on appropriate fixtures or systems;
(12) operate free-standing
appliances;
(13) inspect private water supply
systems, swimming pools, or pressure tanks;
(14) inspect the gas supply
system for leaks; or
(15) inspect for sewer
clean-outs;
§535.230. Standards of
Practice: Inspection Guidelines for Electrical Systems.
(a) Service entrance
and panels. The inspector shall:
(1) inspect service
entrance cables and report as in need of repair deficiencies in the
integrity of insulation, drip loop, separation of conductors at
weatherheads and clearances;
(2) report as in need
of repair a drop, weatherhead or mast that is not securely fastened;
(3) report as in need
of repair the lack of a grounding electrode conductor in the service where
visible, or the lack of secure connection to the grounding electrode or
grounding system;
(4) report as in need
of repair accessible main or subpanels that are not secured to the
structure or appropriate for their location (weather-tight if exposed to
weather, appropriate clearances and accessibility), do not have inside
covers (dead fronts) in place , do not have conductors protected from the
edges of metal panel boxes, do not have trip ties installed on labeled 240
volt circuits, do not have proper fasteners or do not have knockouts
filled ;
(5) inspect and report
as in need of repair deficiencies in the type and condition of the wiring
in the panels, in the compatibility of overcurrent protectors for the size
of conductor being used and in sizing of listed equipment of overcurrent
protection and conductors, when power requirements for listed equipment
are readily available and breakers are labeled;
(6) report as in need
of repair a panel that is installed in a hazardous location, such as a
clothes closet;
(7) report as in need
of repair the absence of appropriate connections, such as copper/aluminum
approved devices, pig-tailed connections or crimp connections; and the
absence of anti-oxidants on aluminum conductor terminations; and
(8) report as in need
of repair the lack of main disconnect(s).
(b) Specific limitations for
service entrance and panels. The
inspector is not required to do the following:
(1) determine service capacity
amperage or voltage or the capacity of the electrical system relative to
present or future use;
(2) determine the insurability of
the property;
(3) conduct voltage drop
calculations; or
(4) determine the accuracy of
breaker labeling.
(c) Branch circuits,
connected devices and fixtures. The inspector shall:
(1) report the type of
branch circuit wiring;
(2) inspect all
accessible receptacles and report as in need of repair a receptacle in
which:
(A) power is not
present;
(B) polarity is
incorrect;
(C) the unit is not
grounded, if applicable;
(D) there is evidence
of arcing or excessive heat;
(E) the unit is not
secured to the wall;
(F) the cover is not
in place; or
(G) ground fault
circuit interrupter devices are not properly installed as set forth by the
current edition of the National Electric Code, publication 70A of the
National Fire Protection Association, or do not operate properly as shown
by use of a separate testing device;
(3) operate all
accessible wall and appliance switches and report as in need of repair a
switch that:
(A) does not operate
or is damaged;
(B) displays evidence
of arcing or excessive heat; or
(C) is not fastened
securely with cover in place.
(4) inspect installed
fixtures including lighting devices and ceiling fans;
(5) report as in need
of repair an inoperable or missing fixture;
(6) report as in need
of repair deficiencies in exposed wiring, wiring terminations, junctions
and junction boxes;
(7) report as in need
of repair deficiencies or absences of conduit in appropriate locations or
conduit that is not terminated securely;
(8) report as in need
of repair appliances and electrical gutters that do not have proper
bonding;
(9) report as in need
of repair subpanels that are not properly bonded and grounded;
(10) report as in need
of repair the lack of disconnects in appropriate locations;
(11) inspect (if
branch circuit aluminum wiring is discovered in the main or subpanels) a
random sampling of accessible receptacles and switches and report as in
need of repair the absence of appropriate connections, such as
copper/aluminum approved devices, pig-tailed connections or crimp
connections;
(12) report as in need
of repair the improper use of extension cords; and
(13) report as in need
of repair the absence of, or deficiencies in, the installation and
operation of smoke or fire detectors not connected to a central alarm
system.
§535.231. Standards of
Practice: Optional Systems.
(a) Scope. This
section covers other systems and attachments that an inspector may
inspect. The inspector may need special knowledge or tools to perform
these inspections. It is the responsibility of the inspector to be
properly informed and know current and safe procedures for inspecting the
items described in this section. The inspector shall determine and provide
a report of the condition of the equipment, systems, parts or components
by visual observation and operation in normal modes and operating range
noted at the date and time of the inspection. If an inspector agrees to
inspect a component described in this section, §535.227 of this title
(relating to Standards of Inspection: General Provisions) applies to the
inspection.
(b) Inspection
guidelines for gas lines. The inspector shall:
(1) inspect and report
as in need of repair deficiencies in the condition and type of all
accessible and visible gas piping; and
(2) test gas lines by
using a local or an industry-accepted procedure.
(c) Specific limitations for gas
lines. The inspector is not
required to inspect sacrificial anode bonding or for its existence.
(d) Inspection
guidelines for outbuildings. The inspector shall:
(1) inspect the
building and report as in need of repair water penetration or deficiencies
in structural performance; and
(2) report as in need
of repair deficiencies in electrical, plumbing, heating, ventilation or
air-conditioning systems that the standards of practice would require the
inspector to report for the principal structure.
(e) Inspection
guidelines for outdoor cooking equipment. The inspector shall:
(1) report the energy
source and operate the unit;
(2) report as in need
of repair deficiencies in operation, control knobs, handles, burner bars,
grills, box, rotisserie (if present) and heat diffusion material;
(3) report as in need
of repair a unit or pedestal that is not stable;
(4) report as in need
of repair gas units that use improper materials for the gas branch line
and the connection to the appliance; and
(5) report as in need
of repair a gas unit that has no shut-off valve, an inaccessible valve or
a valve that leaks;
(f) Inspection
guidelines for lawn and garden sprinkler system. The inspector shall:
(1) operate all zones
or stations on the system manually;
(2) report as in need
of repair deficiencies in water flow or pressure at the circuit heads;
(3) report as in need
of repair surface water leaks, the absence or improper installation of
anti-siphon valves and backflow preventers or the absence of shut-off
valves;
(4) inspect and report
as in need of repair deficiencies in the condition and mounting of the
control box and visible wiring; and
(5) report as in need
of repair deficiencies in the operation of each zone and associated
valves, spray head patterns and areas of non-coverage within the zone.
(g) Specific limitations for lawn
and garden sprinkler system. The
inspector is not required to inspect the automatic function of the timer
or control box, the rain sensor or the effectiveness and sizing of
anti-siphon valves or backflow preventers.
(h) Inspection
guidelines for private water wells. The inspector shall:
(1) operate at least
two fixtures simultaneously;
(2) report the type of
pump and type of storage equipment;
(3) report as in need
of repair deficiencies in water pressure and flow and operation of
pressure switches;
(4) inspect and report
as in need of repair deficiencies in the condition of visible and
accessible equipment and components;
(5) report as in need
of repair wiring that is improper or lacks circuit protection;
(6) report as in need
of repair deficiencies in the well head, including improper site drainage;
(7) recommend, or
arrange to have performed, a coliform analysis; and
(8) report the
proximity of any known septic system.
(i) Specific limitations for
private water wells. The
inspector is not required to do the following:
(1) open, uncover or remove the
pump, heads, screens, lines or other component parts of the system;
(2) determine water quality or
potability or the reliability of the water supply or source; or
(3) locate or verify underground
water leaks.
(j) Inspection
guidelines for Individual private sewage systems (septic systems). The
inspector shall:
(1) report as in need
of repair deficiencies in accessible or visible components of the system
at the time of the inspection;
(2) operate plumbing
fixtures and report as in need of repair deficiencies in functional flow;
(3) walk over the area
of tanks and fields or beds and report as in need of repair any visual or
olfactory evidence of effluent seepage or flow at the surface of the
ground;
(4) report as in need
of repair areas of inadequate site drainage around or adjacent to the
system;
(5) report the
proximity of any known water wells; underground cisterns; water supply
lines; streams, ponds and lakes; sharp slopes or breaks; easement lines;
property lines; soil absorption systems; swimming pools or sprinkler
systems.
(6) inspect the
operation of the system;
(7) report the lack of
visible access to tanks;
(8) report the type of
the system, if possible, and the location of the drainfield; and
(9) report as in need
of repair aerators or dosing pumps that do not operate or equipment that
is improperly wired.
(k) Specific limitations for
individual private sewage systems (septic systems).
The inspector is not required to do the following:
(1) excavate or uncover the
system or its components to determine the size, adequacy or efficiency of
the system; or
(2) determine the type of
construction used unless readily known without excavation or destructive
examination.
(l) Inspection
guidelines for swimming pools and equipment (spas and hot tubs). The
inspector shall:
(1) report the type of
pool construction;
(2) report as in need
of repair deficiencies in pool surfaces,
(3) report as in need
of repair deficiencies in tiles, copings and decks;
(4) report as in need
of repair deficiencies in slides, steps, diving boards and other
equipment;
(5) report as in need
of repair deficiencies in drains, skimmers and valves;
(6) report as in need
of repair pool lights that are missing, do not function or lack ground
fault circuit interrupter protection;
(7) report as in need
of repair pump motors, controls, and sweeps that do not function or lack
proper wiring and circuit protection;
(8) when inspecting a
heater, report as in need of repair deficiencies that the standards of
practice would require the inspector to report for a heating system;
(9) report as in need
of repair gas heaters that use improper materials for the branch line and
the connection to the appliance;
(10) report as in need
of repair a gas unit that has no shut-off valve, an inaccessible valve or
a valve that leaks;
(11) report as in need
of repair a pump motor, blower or other electrical equipment, if visible,
that lacks external grounding;
(12) report as in need
of repair above-ground water leaks or deficiencies in the filter tank or
pressure gauge; and
(13) report as in need
of repair the absence of, or deficiencies in, fences, gates or enclosures.
(m) Specific limitations for
swimming pools and equipment (spas and hot tubs).
The inspector is not required to the following:
(1) dismantle or otherwise open
any components or lines;
(2) uncover or excavate any lines
or otherwise concealed components of the system or determine the presence
of sub-surface leaks;
(3) fill the pool, spa or hot tub
with water;
(4) determine the presence of
sub-surface water tables; or
(5) inspect ancillary
equipment such as computer controls, covers, chlorinators or other
chemical dispensers, or water ionization devices or conditioners other
than required by this section. This agency hereby certifies that the
adoption has been reviewed by legal counsel and found to be a valid
exercise of the agency’s legal authority. Call Today to Schedule an Inspection of Your Home... Phone: 409-737-1190 (Galveston) Phone: 281-996-1846 (Houston) Request an email quote: info@scinspect.com Website Comments: mark@scinspect.com If you would be interested in a home inspection as a measure to protect your investment and family, please call South Coast Inspections anytime. If you have a friend or family member that may be interested in our services, please tell them about South Coast Inspections.